- Contact Person : Mr. Chen Power
- Company Name : Yatai Electrical Group Co., Ltd.
- Tel : 0086-577-89008222
- Fax : 0086-577-89736535
- Address : Zhejiang,Wenzhou,Liushi,Yueqing
- Country/Region : China
- Zip : 325604
ZN63(VS1)-12KV Embedded Poles Type Indoor HV VCB
ZN63(VS1)-12KV Series Embedded Poles Type Indoor HV Vacuum Circuit Breaker
ZN63(VS1)-12 Series Embedded Poles Type Indoor HV Vacuum Circuit Breaker, adopt solid insulation structure, use of advanced solid epoxy sealing technology, the first time, the vacuum interrupter. A leading electrical circuit. insulation and other support to become an integrated combination of solid seal pole. Successfully from a fundamental solution of the vacuum breaker gas environment, tolerance issues, make it more broad. Integrated solid-pole closure of the fluent use of a self-ventilation technology, cleverly solved the structure of solid insulation caused by heat dissipation.
ZN63(VS1)-12 Series Embedded Poles Type Indoor HV Vacuum Circuit Breaker is the first to achieve maintenance-free concept of a circuit breaker. Its high-life vacuum interrupter chamber as well as solid cast epoxy sealing technology applications to ensure an integrated solid-pole sealed maintenance-free, with high reliability using permanent magnetic actuator of the actuator to ensure maintenance-free, electronic control parts reject the traditional auxiliary switch and replaced by photoelectric proximity switches, and use the whole power and intelligent electronic control unit ensures that electronically controlled part of the maintenance-free.
The use of environmental conditions:
1.Ambient temperature: not higher than +40 °C, not less than -15°C(at -30 °C to allow storage and transportation).
2. Altitude: not exceed 1000m.
3. Relative humidity: daily average of not more than 90%, month average of not more than 90%.
saturated vapor pressure daily average of not more than 2.2 × 10-3MPa, month average not more than 1.8 × 10-3MPa.
4. Earthquake intensity: not more than eight.
5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.
Mainly technical parameters | ||||||
NO | Item | Units | parameters | |||
1 | Rated voltage | KV | 12 | |||
2 | Rated insulation level | Rated Lightning Impulse voltage tolerance | KV | 75 | ||
1min Frequency voltage | 42 | |||||
3 | Rated short-circuit breaking current | KA | 20/25 | 31.5 | 40 | |
4 | Rated current | A | 630 | 630 1250 | 1250 1600 | |
1250 | 1600 2000 | 2000 2500 | ||||
2500 3150 | 3150 4000 | |||||
5 | Rated thermal stability of current (RMS) | KA | 20/25 | 31.5 | 40 | |
6 | Dynamic Stability rated current (peak) | 63 | 80 | 100 | ||
7 | Rated short-circuit closing current (peak) | 63 | 80 | 100 | ||
8 | Rated short-circuit breaking current breaking number | times | 50 | |||
9 | Frequency tolerance of the secondary circuit voltage (1min) | V | 2000 | |||
10 | Rated operating sequence | 0-0.3s-CO-180s-CO | ||||
0-180s-CO-180s-CO(40kA) | ||||||
11 | Rated thermal stabilization time | S | 4 | |||
12 | Rated a single / back-to-back electric current breaking device group | 630/400 800/400(40KA) | ||||
13 | Mechanical life | Times | 10000 |
ZN63(VS1)-12KV Embedded Poles Type Indoor HV VCB